Core identification instrumentation cables
Pair - Black - Light Blue
Triple - Black - Light Blue - Brown
Quad - Black - Light Blue - Brown - Grey
BRAND: Draka Norsk Kabel AS
RFOU(i) 150/250(300)V
EPR/EPR/TCWB/EVA
NEK TS 606 CodeS1/S5
Operating temperature : 90°C
Operating Voltage : 150/250(300)V
Application
Fixed installation for instrumentation, communication, Control and alarm systems in both EX (Zone 0, 1 & 2)- and safe areas.
Meets the mud resistant requirements in NEK TS 606:2009.
Standards Applied
IEC 60092-376 (2003-05) - Design
IEC 60228 class 2 - Conductor
IEC 60092-360 - Insulation
IEC 60092-360 - Sheath
IEC 60332-1-2 - Flame Retardant
IEC 60332-3-22 - Flame Retardant
IEC 60754-1,2 - Halogen Free
IEC 61034-1,2 - Low Smoke
ORIGIN: KOREA
Cable Designation (P105)
0.6/1kV BFOU, BFCU, BFBU
Application Standard
- Design guide : NEK-606 & IEC 60092-353
- Flame retardant : IEC 60332-1 & IEC 60332-3 Category A
- Fire resistance : IEC 60331-21(90min) IEC 60331-1,-2(120min)
- Halogen content : IEC 60754-1, 0.5%↓
- Cold bend / impact : CSA C22.2 No. 2556 or IEC 60092-350 Annex.E Method 1 (-40℃/-35℃)
- Mud / Oil resistant : NEK 606 (Category a,b,c,d)
- Mud resistant : NEK-606 (Mud type only)
- Smoke light transmittance : IEC 61034, 60%↑ 0.6/1kV BFOU
- Sunlight (UV) resistant : UL 1581
ORIGIN: KOREA
Cable Designation (P101)
0.6/1kV RFOU, RFCU, RFBU
Application Standard
- Design guide : NEK-606& IEC 60092-353
- Flame retardant : IEC 60332-1 & IEC 60332-3 Category A
- Halogen content : IEC 60754-1, 0.5%↓
- Cold bend / impact : CSA C22.2 No. 2556 or IEC 60092-350 Annex.E Method 1 (-40℃/-35℃)
- Mud / Oil resistant : NEK 606 (Category a,b,c,d)
- Smoke light transmittance : IEC 61034, 60%↑ - Sunlight (UV) resistant : UL 1581
ORIGIN : KOREA
Cable Designation (P111)
0.6/1kV RU
Application Standard
- Design guide : NEK-606 & IEC 60092-353
- Flame retardant : IEC 60332-1 & IEC 60332-3 Category A
- Halogen content : IEC 60754-1, 0.5%↓ - Cold bend / impact : CSA C22.2 No. 2556 or IEC 60092-350 Annex.E Method 1 (-40℃/-35℃)
- Mud / Oil resistant : NEK 606 (Category a,b,c,d)
- Smoke light transmittance : IEC 61034, 60%↑ 0.6/1kV RU
- Sunlight (UV) resistant : UL 1581
ORIGIN: KOREA
Cable Designation (P102, P103, P104) :
3.6/6KV RFOU, RFBU, RFCU
6/10KV RFOU, RFBU, RFCU
8.7/15KV RFOU, RFBU, RFCU
Application Standard
- Design guide : NEK-606 & IEC 60092-354
- Flame retardant : IEC 60332-1 & IEC 60332-3 Category A
- Halogen content : IEC 60754-1, 0.5%↓
- Cold bend / impact : CSA C22.2 No. 2556 or IEC 60092-350 Annex.E Method 1 (-40℃/-35℃)
- Mud / Oil resistant : NEK 606 (Category a,b,c,d) - Smoke light transmittance : IEC 61034, 60%↑ - Sunlight (UV) resistant : UL 1581
1. Conductor AWG24 (7xAWG32) tinned Cu
2. Insulation
Material Polyethylene
Diameter over insulation 1.73 ± 0.05 mm
Colour of insulation
Pair #1: White/blue and blue/white
Pair #2: White/orange and orange/white
Pair #2: White/green and green/white
3. Filler : Polypropylene
4. Foil (Z-fold®)
Material Aluminium / Polyester
Thickness 9 / 23 µm
5. Drainwire AWG20 (7xAWG28) tinned Cu
6. Braiding
Material 0.122 mm tinned Cu
Coverage 90%
7. Sheath
Material FRNC
Colour Chrome (like RAL 7037)
Nominal Wall thickness 0.89 mm
Nominal diameter over sheath 9.10 mm
• Power and control cables
• Special applications